Coordinated Low-Voltage Ride-Through Control Strategy for Flywheel Energy Storage Systems

  • Dahai Guo
  • , Guangchen Liu
  • , Jianwei Zhang
  • , Guizhen Tian
  • , Sufang Wen
  • , Zicheng He
  • , Yan Wang

Research output: Journal PublicationArticlepeer-review

Abstract

To address DC-link voltage fluctuation, active-power imbalance between the machine side and the grid side, and double-frequency distortion in the grid current of a flywheel energy storage system (FESS) under symmetrical and asymmetrical voltage sag faults, this paper proposes a coordinated control strategy for the machine-side and grid-side converters to enhance low-voltage ride-through (LVRT) capability. Taking the DC-side energy imbalance as the coordination criterion, the machine-side converter adopts an online active-current-command reconstruction method based on cascaded limiting of DC-link voltage deviation. Under reactive-power-priority support and constrained active-power output on the grid side, the FESS can actively adjust its active-current command according to the DC-side energy state, thereby suppressing DC-link overvoltage/undervoltage and restoring the power balance between the machine side and the grid side. On the grid side, an improved linear active disturbance rejection control (LADRC) is introduced into the current inner loop. By optimizing the structure of the extended state observer, the observation and compensation capability for double-frequency disturbances is enhanced, thus improving grid-current quality under asymmetrical faults. In this way, power rebalancing between the machine side and the grid side, DC-link voltage stabilization, and grid-current disturbance suppression are incorporated into a unified coordinated control framework. Hardware-in-the-loop experimental results show that the proposed strategy can maintain DC-link voltage stability during both symmetrical and asymmetrical voltage sags, while keeping the maximum grid-current total harmonic distortion (THD) below 0.13%. Under asymmetrical voltage sag, the improved LADRC reduces the maximum interphase peak-current deviation from approximately 52 A under conventional PI control to 4.57 A, corresponding to a reduction of about 91.2%. These results indicate that the proposed strategy can effectively enhance DC-link voltage stabilization and improve grid-current quality during faults.
Original languageEnglish
Article number5388
JournalApplied Sciences
Volume16
Issue number11
DOIs
Publication statusPublished - 28 May 2026
Externally publishedYes

Free Keywords

  • flywheel energy storage system
  • low-voltage ride-through
  • coordinated control
  • DC-link voltage deviation control
  • improved linear active disturbance rejection control